Site Map   |   News   |   Contact Us

.
 
  >  HOME
  >  ABOUT US
  >  PRODUCTS
      - Solar Panels
      - Solar Batteries
      - Solar Water Heaters
      - Wind Turbines
      - Grey Water Recycling
      - Under Tile Heating
           - Flooring
           - Heating
           - Mat Design
           - Brief Specifications
      - Off-Grid Systems
      - On-Grid Systems
      - Inverters
      - Mounting Systems
      - Cables & Connectors
  >  SERVICES
  >  FINANCING OPTIONS
  >  SAMPLE INSTALLATIONS
  >  LIVE PV DATA
  >  LINKS & DOWNLOADS
  >  CONTACTS US
 

Undertile Heating
Radiant Floor Heating Systems

Before fitting Warmup’s Undertile Heater there are several considerations you must bear in mind with regards to heat:

• Will the undertile heater be the main heat source in the room?
• Are you aware of how much time your floor will take to heat up?
• Have you checked out the running costs/power consumption?
 

Heating Capabilities
Warmup Undertile Heating Mats can be used as the only heat source in rooms that comply with insulation levels set out in current building regulations and where 100% of the floor area is covered by the heating system.

In rooms (such as bathrooms or kitchens) where the entire floor is not covered, or in rooms where the heat loss is very high (such as conservatories), additional heating may need to be installed

A heat loss calculation should be preformed to determine exactly the amount of heat required to heat the room. Then, by measuring the area to be heated and using the table below; you can calculate whether additional heating is required.

Heating
Mat

kW
output

PFM1.5

230

PFM02

345

PFM03

460

PFM04

667

PFM05

759

PFM06

897

PFM07

1012

PFM08

1265

PFM09

1380

PFM10

1518

PFM11

1633


Heat-Up Times
Heat-up times depend on such variables as the thickness of the tiles and the design of the subfloor.

Subfloor construction

Heat-up time

WBP Plywood on timber

1 hr

Insulated concrete - insulation under screed

2 - 5 hrs

Un-insulated concrete

2 - 8 hrs

Concrete with insulated tile backer board- 10mm

1 hr

Concrete with insulated tile backer board - 50mm

0.5 hr


Layout
The Warmup Undertile Heating Mat is most suitable for larger regular shaped areas. The Warmup Installation Manual provides a useful guide to heater layout; however it may be necessary to alter this slightly to suit your particular installation.

To work out how much matting you will need, divide your floor space into rectangles (see sample layout picture). From that you can see how many mats you will need. The mat must not be laid under permanent fixtures (e.g. bathtubs, cupboards, etc), so exclude these from your calculations.

Multiple Undertile Heating Mats
Before installing, ensure you have the correct number and size of heaters for the area you wish to heat. You may wire a maximum of 25m˛ Heating Mat through one Warmup TSTAT Thermostat with the mats joining in parallel at the thermostat.

When laying more than one mat it is important to remember the following:
• The mats are joined in parallel only at the thermostat or in a junction box. DO NOT attach one
   mat to another in series.
• The heating wires of the mat may never be shortened or cut.
• Never leave any surplus mat rolled up underneath the flooring.

Areas in excess of 25 square metres
If the area to be heated exceeds 25m˛, then you must install Warmup Undertile Heating Mat using multiple thermostats.

 
 
 
2/3 Tal-Balal Road, Xwieki L/O Gharghur, Malta / Tel: +356 21424750 or +356 27424750
E-Mail - info@solarmalta.com - (c) 2008 - Terms & Conditions

Website Designed by Storm Design - Malta web design